ZW20-12 Series Ma waho High Voltage Vacuum Circuit Breaker

ʻO ka wehewehe pōkole:


Huahana Huahana

Huahana Huahana

ʻO ZW20-12 waho HV kaapuni kaʻapuni kaʻapuni he 3-phase AC 50Hz 12kV nā lako hoʻololi waho.

♦ Ke ala hoʻokomo: pole i kau ʻia;

♦ ʻAno Pole: pole i hoʻohui ʻia;

♦ Noi: waho 12kV substation, mana mea kanu.

♦ ʻAno hana: manual, uila, mamao mamao.

 

Nā Kūlana Kaiapuni

♦ Ke kiʻekiʻe:

♦ Ea wela: -40°C~ +40°C; hoʻololi i ka mahana o kēlā me kēia lā

♦ Ka makani makani

♦ Ka pae pelapela: IV;

♦ Nā wahi hoʻokomo: ʻAʻohe ahi, pōʻino pahū, ʻino kemika koʻikoʻi a i ʻole haʻalulu koʻikoʻi;

♦ Ka ikaika o ke olai:

 

Nā Kūlana Kūlana Nui

ʻAʻOLE

'ikamu

Unite

Waiwai

1 Volta koho

kV

12

2 ʻO ke alapine ikaika e kū i ka volta (1min) (maloʻo) inter-phase, honua/haʻi;

kV

42/48

(wet) inter-phase, honua

34

3 Kū'ē ka uila uila (interphase, earth/fracture)

kV

75/85

4 Kuhi ʻia i kēia manawa A

630,1250

5 Ua helu pinepine ʻia

Hz

50

6 Hoʻoholo ʻia ka ʻāwīwī pōkole pōkole

kA

20, 25

7 Ua helu ʻia ka waiwai kiʻekiʻe e kū i kēia manawa (peak)

kA

50, 63

8 Kuhi ʻia ka manawa pōkole e kū i kēia manawa

kA

20, 25

9 Hoʻoholo ʻia i kēia manawa pōkole pōkole

kA

50, 63

10 Hoʻoholo ʻia ka lōʻihi kaapuni pōkole S

4

11 Hoʻoholo ʻia ke kaʻina hana Manawa

O-0.3S-CO-1 80S-CO

12 Helu haʻi kaapuni pōkole i kēia manawa Manawa

30

13 Ola mīkini Manawa

10000

14 ʻO ka volta hana i helu ʻia (hiki ke hana ʻia) IN

220

15 Ka manawa wehe

ms

≤80

16 Ka manawa pani

ms

≤120

17 Ka wā hoʻomaha piha

ms

≤100

18 Hoʻopili ʻia ka hoʻouka ʻana o ke kaula i kēia manawa

A

50

19 Papa

E2~C2~M2(10000)

20 Helu haʻi kaapuni pōkole i kēia manawa Manawa

30

Ke kaha kiʻi a me ka nui o ka hoʻonohonoho ʻana (unit: mm)

svv

Nā ala hoʻokomo

svv


  • Mua:
  • Aʻe: